Object
Identifier
Name
Description
* System=sum of three phases
5120
kVAR Demand System Max
System Maximum Instantaneous kVAR Demand (kVA, resettable). It
displays the default value after a CAM until 1 demand window
elapses. After a power cycle or CPU reset the value is not reset but
it does not update again until 1 demand window elapses.
(Unsigned/Absolute)
5130
kVAR Demand System Now
Average kVAR demand for most recent window (resettable).
Displays the default value after a CAM or reset, or power cycle.
Updates every min thereafter. True demand value takes a demand
period to get to actual value. (Unsigned/Absolute)
6010
kVARh System
System Total Reactive Energy (Unsigned/Absolute)
7000
kVAh System Total
System Total Apparent Energy (Unsigned/Absolute)
8000
kVA System
System Total Apparent Power (kVA). Unsigned absolute (ABS) value
of ABS (kVA L1) + ABS (kVA L2) + ABS (kVA L3)
8001
kVA System Net
System Net Apparent Power (kVA). Signed net value of (kVA L1) +
(kVA L2) + (kVA L3)
8010
kVA L1
Individual Phase Apparent Powers (kVA) (signed)
8020
kVA L2
“Sign is set to the sign of the kW
8030
kVA L3
“
8040
kVA Demand System Max
System Maximum Instantaneous kVA Demand (kVA, resettable). It
displays the default value after a CAM until 1 demand window
elapses. After a power cycle or CPU reset the value is not reset but
it does not update again until 1 demand window elapses.
(Unsigned/Absolute)
8050
kVA Demand System Now
Average kVA for most recent demand window (resettable). Displays
the default value after a CAM or reset, or power cycle. Updates
every min thereafter. True demand value takes a demand period to
get to actual value. (Unsigned/Absolute)
9000
Displacement PF System
System Total Power Factor (PF) (Signed)
9030
Apparent PF System
System Total Power Factor (PF) (Signed)
9060
Displacement PF L1
Individual Phase displacement Power Factor (PF)
9090
Displacement PF L2
“
9120
Displacement PF L3
“
91