Object
Identifier
Name
Description
* System=sum of three phases
1160
kW L1
Individual Phase True Power (kW) (Signed)
1190
kW L2
“
1220
kW L3
“
2000
kWh System Total
System True Energy (kWh) (Unsigned/Absolute)
3000
Volts Line to Line Average
Voltage Line to line Average
3010
Volts Line to Neutral Average
Voltage Line to neutral Average
3020
Volts L1 to L2
Individual Phase to Phase Voltages
3030
Volts L2 to L3
“
3040
Volts L1 to L3
“
3050
Volts L1 to Neutral
Individual Phase to Neutral Voltages (V)
3060
Volts L2 to Neutral
“
3070
Volts L3 to Neutral
“
4010
Amps System Average
Average of all phases.
4020
Amps L1
Individual Phase Currents (A)
4030
Amps L2
“
4040
Amps L3
“
5000
kVAR System
System Total Reactive Power (kVAR). Unsigned absolute (ABS) value
of ABS (kVAR L1) + ABS (kVAR L2) + ABS (kVAR L3)
5001
kVAR System Net
System Total Reactive Power (kVAR). Signed net value of (kVAR L1)
+ (kVAR L2) + (kVAR L3)
5030
kVAR L1
Individual Phase Reactive Energy LSW (kVARh) (Signed)
5060
kVAR L2
“
5090
kVAR L3
“
90