Object
Identifier
Name
Description
13020
(PS3 only)
Port 1 output control when
used as an on/off—open/closed
switch
0 = output LOW (closed) 1 = output HIGH (open) [default]
Object 13100 present value must = 0 to use
13030
(PS3 only)
Port 2 output control when
used as an on/off—open/closed
switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Object 13150 present value must = 0 to use
13040
(PS24 only)
Configures the pulse input for
I/O port 1
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling edges are ignored. If
pulse output is enabled, it is disabled when this configuration is set.
2 = falling edge, pulse counter increments, rising edges are ignored. If
pulse output is enabled, it is disabled when this configuration is set.
3 = both edges pulse counter increments. If pulse output is enabled,
it is disabled when this configuration is set. (Note when pulse is off,
I/O control is enabled)
Setting this register to a value other than 0, forces register 45110 to
0.
13050
(PS24 only)
I/O port 1 pulse input
accumulator
Scaled pulse
13060
(PS24 only)
I/O port 1 pulse input
x1000 decimal fraction of scale factor
13070
(PS24 only)
Configures the pulse input for
I/O port 2
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling edges are ignored. If
pulse output is enabled, it is disabled when this configuration is set.
2 = falling edge, pulse counter increments, rising edges are irnored. If
pulse output is enabled, it is disabled when this configuration is set.
3 = both edges pulse counter increments. If pulse output is enabled,
it is disabled when this configuration is set. (Note when pulse is off,
I/O control is enabled)
Setting this register to a value other than 0, forces register 45210 to
0.
13080
(PS24 only)
I/O port 2 pulse input
accumulator
Scaled pulse
13090
(PS24 only)
I/O port 2 pulse input scaling
x1000 decimal fraction of scale factor
13100
(PS3 only)
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
88