a)
Select the correct device from the list of IP Addresses.
b)
Click
Setup
. The Logger Network Setup dialog box displays, below.
The
Setup
button displays the Logger Network Setup dialog box where network address information
is entered.
See your network administrator before making changes.
c)
Select the
Use DHCP
checkbox. The Dynamic Host Configuration Protocol is then used to
populate the IP Address, Subnet Mask, and Gateway Address fields.
d)
Select Modbus from the
Mode
drop-down list.
e)
Click
Update Logger
.
ViewPoint displays the following message when the connection is successful.
5)
Enter the
Port
connected to the PowerScout. A checkbox is available to make the port the default.
Different networks may require different ports.
See your network administrator.
D
ID
Y
OU
K
NOW
?
DENT Instruments
uses well-known and registered
port numbers for BACnet (47808)
and Modbus (502) assigned by the
IANA (Internet Assigned Numbers
Authority).
21