Modbus
Register
Offset
ViewPoint Name
Description
40023
22
Amps L2
"
40024
23
Amps L3
"
40025
24
kW System Avg
Equals KWH_SYSTEM_L&M ÷ (TimeSinceReset_L&M seconds
/3600 seconds/Hr) (resettable)
40026
25
kW Demand System Min
System Minimum Demand (kW, resettable), It displays the default
value after a CAM until 1 demand window elapses. After a power
cycle or CPU reset the value is not reset but it does not update
again until 1 demand window elapses.
40027
26
kW Demand System Max
System Max Demand (kW, resettable). Behaves as 40026.
Table H-2: ViewPoint Register Descriptions
VERIS
M
ULTIPLIERS
Address
Units
≤ 100A
101 – 400A
401 – 800A
801 – 1600A 1601 – 32,000A
40001
kWH LSB
7.8125exp-3
0.03125
0.0625
0.125
0.25
40002
kWH MSB
512
2048
4096
8192
16384
40003
kW
0.004
0.016
0.032
0.064
0.128
40004
kVAR
0.004
0.016
0.032
0.064
0.128
40005
kVA
0.004
0.016
0.032
0.064
0.128
40006
aPF
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
40007
VOLTS L-L
0.03125
0.03125
0.03125
0.03125
0.03125
40008
VOLTS L-L
0.015625
0.015625
0.015625
0.015625
0.015625
40009
AMPS
3.9063exp-3
0.015625
0.03125
0.0625
0.125
40010
kW L1
0.001
0.004
0.008
0.016
0.032
40011
kW L2
0.001
0.004
0.008
0.016
0.032
40012
kW L3
0.001
0.004
0.008
0.016
0.032
40013
aPF L1
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
103