Connecting a PowerScout™ Meter
PowerScout meters have the following connections:
Either a three-wire connector for the RS-485 BACnet/Modbus link or an Ethernet connector.
The PowerScout 3+ has four hardwired voltage leads for connecting to voltage sources (L1, L2,
L3, and Neutral). The PowerScout 24 has the four voltage connections but the leads are not
supplied.
PowerScout meters are self-powered from L1 and L2.
Up to three (PS3 Plus) current transformers (CTs), twenty-four (PS24) current transformers
(CTs).
Digital output ports. The ports can be used to output kWh, kVARh, or kVAh pulses to external
devices, or to toggle on and off to control a remote device or relay.
Completing the Wiring Connections—Ethernet/RS-485, Voltage Leads
and CTs
1)
Connect with an Ethernet cable to a computer.
-or-
Connect the RS-485 adapter to the computer using
the USB cable and by inserting each white ferrule
into the appropriate opening on the PowerScout
meter. The red wire inserts in (+), the black wire in
(-) and the green wire in (S).
D
ID
Y
OU
K
NOW
?
The
PowerScout has an internal,
non-user replaceable .5 Amp
fuse protection.
14