Modbus Output Port Registers
Refer to the following two tables to configure the PowerScout output ports when using the Modbus
protocol.
PS3
Modbus
Register
PS24
Modbus
Register
Offset
Register Name
Detailed Description
44402
45302
4401/5301
Port 1 output control
when used as an on/off—
open/closed switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Register 45110 must = 0 to use
45110
45310
5109/5309
Digital Port 1
Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an
on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
45111
45311
5110/5310
Port 1 pulse output relay
type
0 = normally open (HIGH)
1 = normally closed (LOW)
Table F-2: Modbus Digital Port 1 Pulse Output
Modbus
Register
Offset
Register Name
Detailed Description
44403
4402
Port 2 output control when used
as an on/off—open/closed switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Register 45210 must = 0 to use
45210
5209
Digital Port 2 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
45211
5210
Port 2 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
Table F-3: PS3 Modbus Digital Port 2 Pulse Output