PowerScout™ Meter Safety Summary and Specifications
This general safety information is to be used by both
the Logger operator and servicing personnel. DENT
Instruments, Inc. assumes no liability for user’s
failure to comply with these safety guidelines.
PS3P
PS3E
PS24-D
PS48-D
PS24-N
PS48-N
All items conform to the following:
Conforms to UL Std 61010-1
Certified to CSA Std C22.2 No. 61010-1
The XXXX-N devices need to be installed in a user-supplied UL Listed/Recognized enclosure in order to comply with NEC
and local electrical codes.
The PowerScout is an Over-Voltage Category III device.
CAUTION:
THIS METER MAY CONTAIN LIFE THREATENING VOLTAGES. QUALIFIED PERSONNEL MUST DISCONNECT
ALL HIGH VOLTAGE WIRING BEFORE USING OR SERVICING THE METER.
WARNING
Use of this device in a manner for which it is not intended may impair its means of protection.
Symbols on Equipment
Denotes caution. See manual for a description of the meanings.
When connecting the PowerScout to an AC load, follow these steps in sequence to prevent a shock hazard.
1.
De-energize the circuit to be monitored.
2.
Connect the CTs to the phases being monitored.
3.
Connect the voltage leads to the different phases. Use proper safety equipment (gloves
and protective clothing) as required for the voltages monitored.
DENOTES HIGH VOLTAGE. RISK OF ELECTRICAL SHOCK. LIFE THREATENING VOLTAGES MAY BE PRESENT.
QUALIFIED PERSONNEL ONLY.
DO NOT EXCEED 600V.
This meter is equipped to monitor loads up to 600V. Exceeding this voltage will cause
damage to the meter and danger to the user. Always use a Potential Transformer (PT) for loads in excess of
600V. The PowerScout is a 600 Volt Over Voltage Category III device.