ZL0101-0D
Page 1 of 20
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 0818
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must
control conductive pollution and the possibility of condensation or high humidity. Consider the
enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship with
the environment. Installation category: CAT II or CAT III. Provide a disconnect device to disconnect the
meter from the supply source. Place this device in close proximity to the equipment and within easy
reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the
relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. In the US
and Canada, disconnecting fuse holders can be used. Provide overcurrent protection and disconecting
device for supply conductors with approved current limiting devices suitable for protecting the wiring.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the
device may be impaired.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Product may use multiple voltage/power sources. Disconnect ALL sources before
servicing.
• Use a properly rated voltage sensing device to confirm that power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION.
• Current transformer secondaries must be shorted or connected to a burden at all times.
• Products rated only for basic insulation must be installed on insulated conductors.
• Replace all doors, covers and protective devices before powering the equipment.
Failure to follow these instructions will result in death or serious injury.
A qualified person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and installations, and has received safety
training to recognize and avoid the hazards involved.
NEC Article 100
If this product is used in a manner not specified by the manufacturer, the protection
provided by the product may be impaired. No responsibility is assumed by the
manufacturer for any consequences arising out of the use of this material.
DANGER
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found to
comply with the limits for a class B digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a
residential environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including
interference that may cause undesired operation.
Modifications to this product without the express authorization of the
manufacturer nullify this statement.
WARNING
LOSS OF CONTROL
∙ Assure that the system will reach a safe state during and after a control path failure.
∙ Separate or redundant control paths must be provided for critical control functions.
∙ Test the effect of transmission delays or failures of communication links.
1
∙ Each implementation of equipment using communication links must be individually
and thoroughly tested for proper operation before placing it in service.
Failure to follow these instructions may cause injury, death or equipment damage.
1
For additional information about anticipated transmission delays or failures of the link, refer to
NEMA ICS 1.1 (latest edition).
Safety Guidelines for the Application, Installation, and Maintenance
of Solid-State Control
or its equivalent in your specific country, language, and/or location.
Control system design must consider the potential failure modes of control paths and, for
certain critical control functions, provide a means to acheive a safe state during and after a
path failure. Examples of critical control functions are emergency stop and over-travel stop.
TM
Installation Guide
Power Monitoring
The safety of any system incorporating this equipment is the responsibility of the
assembler of the system.
Product Overview
The E50C1 DIN Rail Power Meter provides a solution for measuring energy data with a single device. Inputs include
Control Power, CT, and 3-phase voltage. The E50C1 supports multiple output options, including solid state relay
contacts, Modbus, and pulse. The LCD screen on the faceplate allows instant output viewing.
The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN 50022. The E50C1
can be mounted with any orientation over the entire ambient temperature range, either on a DIN rail or in a panel.
The meter is not sensitive to CT orientation, reducing installation errors.
E50C1
Compact Power and Energy Meter
Product Identification
Model
Description
Output
DIN Mount (meter only)
Pulse
RS-485 Alarm
E50C1
Modbus output, basic data set
•
•
•
Specifications
MEASUREMENT ACCURACY
Real Power and Energy
IEC 62053-22 Class 0.2S, ANSI C12.20 0.2%
Reactive Power and Energy
IEC 62053-23 Class 2, 2%
Current
0.4% (+0.015% per °C deviation from 25 °C) from 5% to 100% of range; 0.8%
(+0.015% per °C deviation from 25 °C) from 1% to 5% of range
Voltage
0.4% (+0.015% per °C deviation from 25 °C) from 90V
L-N
to 600 Vac
L-L
Sample Rate
2520 samples per second
Data Update Rate
1 sec
Type of Measurement
True RMS up to the 21st harmonic 60 Hz; One to three phase AC system
INPUT VOLTAGE CHARACTERISTICS
Measured AC Voltage
Minimum 90V
L-N
(156V
L-L
) for stated accuracy;
UL Maximum: 600V
L-L
(347V
L-N
)
CE Maximum: 300V
L-N
Metering Over-Range
+20%
Impedance
2.5 MΩ
L-N
/5 MΩ
L-L
Frequency Range
45 to 65 Hz
INPUT CURRENT CHARACTERISTICS
CT Scaling
Primary: Adjustable from 5 A to 32,000 A
Measurement Input Range
0 to 0.333 Vac or 0 to 1.0 Vac (+20% over-range), rated for use with Class 1
voltage inputs
Impedance
10.6 kΩ (1/3 V mode) or 32.1 kΩ (1 V mode)