E50C1 Installation Guide
Modbus Point Map
E50C1 REG.
R/W NV Format
Units
Scale
Range
Description
Integer Data
001
R
NV ULong
kWh
E
0-0xFFFF
Real Energy Consumption (MSR)
Clear via reset register
002
0-0xFFFF
Real Energy Consumption (LSR)
003
R
UInt
kW
W
0-32767
Total Instantaneous Real Power (3 Phase Total)
Configuration
129
R/W
UInt
N/A
Command Register:
- Write 30078 (0x757E) to clear all Energy Accumulators to 0.
- Write 16498 (0x4072) to Clear Pulse Counters to 0.
- Read always returns 0.
130
R/W NV UInt
10,
11,
12,
31,
40
Single Phase: A + N
System Type
(See Manual. Note: only the indicated
phases are monitored for Phase Loss)
Single Phase: A + B
Single Split Phase: A + B + N
3 phase ∆, A + B + C, no N
3 phase Y, A + B + C + N
131
R/W NV UInt
Amps
1-32000
CT Ratio – Primary
Current Inputs
132
R/W NV UInt
1, 3
CT Ratio – Secondary Interface (1 or 1/3 V, may not be user
configurable)
133
R/W NV UInt
100
0.01-320.00 PT Ratio: The meter scales this value by 100 (i.e. entering 200 yields a potential transformer ratio of 2:1). The
default is 100 (1.00:1), which is with no PT attached. Set this value before setting the system voltage (below)
134
R/W NV UInt
82-32000
System Voltage: This voltage is line to line, except for system type 10 which is line to neutral. The meter uses
this value to calculate the full scale power for the analog outputs and pulse configuration (below), and as full
scale for phase loss (register 142). The meter will refuse voltages that are outside the range of 82-660 volts
when divided by the PT Ratio (above).
135
R
NV UInt
kW
W
1-32767
Theoretical Maximum System Power: This read-only value is the theoretical max. power the meter can expect to
see on a service. This value is 100% of scale on the analog output (0-5 Vdc or 4-20 mA), if equipped. The meter
recalculates this value if the user changes the CT size, system type, or system voltage. This integer value has
the same scale as other integer power registers (see register 140 for power scaling).
136
R
UInt
Reserved, always returns 0
137
R/W NV UInt
0,1
Display Units: 0 = IEC (U, V, P, Q, S), 1 = IEEE (default: VLL, VLN, W, VAR, VA)
138
R
SInt
-4 0.0001
-3 0.001
-2 0.01
-1 0.1
0 1.0
1 10.0
2 100.0
3 1000.0
4 10000.0
Scale Factor I (Current)
Scale Factors
Note: These registers contain a signed
integer, which scales the corresponding
integer registers. Floating point registers
are not scaled. Scaling is recalculated
when the meter configuration is changed.
139
R
SInt
Scale Factor V (Voltage)
140
R
SInt
Scale Factor W (Power)
141
R
SInt
Scale Factor E (Energy)