E50C1 Installation Guide
Daisy-chaining Devices to the Power Meter
The RS-485 slave port allows the power meter to be connected in a daisy chain with up to 63 2-wire devices.
–
+
S
120 Ω terminator on the first and last
device of the daisy chain
Shield wire
Notes
• The terminal’s voltage and current ratings are compliant with the requirements of the EIA RS-485 communications
standard.
• The RS-485 transceivers are ¼ unit load or less.
• RS-485+ has a 47 kΩ pull up to +5V, and RS-485- has a 47 kΩ pull down to Shield (RS-485 signal ground).
• Wire the RS-485 bus as a daisy chain from device to device, without any stubs. Use 120 Ω termination resistors at each
end of the bus (not included).
• Shield is not internally connected to Earth Ground.
• Connect Shield to Earth Ground somewhere on the RS-485 bus.
For all terminals:
• When tightening terminals, apply the correct torque: 0.37 to 0.44
ft·lb (0.5-0.6 N·m).
• Use 14-24 gauge (2.1-0.2 mm
2
) wire.
RS-485
Communications
Red
Black
Gray
0.37 to 0.44 ft-lb
(0.5 to 0.6 N-m)
Use 14 to 24 gauge wire
Standard Modbus
Default Settings
Setting
Value
Modbus
Register
Setup Password
00000
–
Reset Password
00000
–
System Type
40 (3 + N) Wye
130
CT Primary Ratio (if CTs are not included)
100A
131
CT Secondary Ratio
1V
132
PT Ratio
1:1 (none)
133
System Voltage
600 V L-L
134
Max. Theoretical Power
(Analog Output: full scale (20mA or 5V))
104 kW
135
Display Mode
1 (IEEE)
137
Phase Loss
10% of System Voltage (60V), 25% Phase to Phase Imbalance
142, 143
Pulse Energy
1 (kWh/pulse)
144
Modbus Address
001
–
Modbus Baud Rate
19200 baud
–
Modbus Parity
None
–