E50C1 Installation Guide
E50C1 REG.
R/W NV Format
Units
Scale
Range
Description
152
R/W NV UInt
0-32767
Power Up Counter.
153
R
NV UInt
0-32767
Output Configuration. E50C1 always returns 0
154
R
UInt
Reserved, returns 0
Floating Point Data
257/258 R
NV Float
kWh
Real Energy Consumption (clear via reset register)
259/260 R
NV Float
kWh
Real Energy Consumption (clear via reset register)
261/262 R
Float
kW
Total Instantaneous Real Power
Invalid or Quiet Not A Number (QNAN) conditions are indicated by 0x8000 (negative zero) for 16 bit integers and 0x7FC00000 for 32 bit floating point numbers.
Floating point numbers are encoded per the IEEE 754 32-bit specifications.