HyCassette-Geko
Electrical Connection
PR-2015-0159-GB • Subject to modifications • R1-11/2015
96
6.14.4 Operating mode
Heating and Cooling
(4-pipe system)
6.14.5 Sensors and control inputs
Fig. 6-45: Fan continuous mode and valve control configuration
Fig. 6-46: Sensor connection
Room or return-air sensor connection (option) or inlet sensor
–
Connecting cable, refer to top note on Page 76.
Pos. 1:
Room or return-air sensor
Pos. 2:
Inlet temperature sensor
•
Connect the sensors in accordance with the wiring diagram.
Return-air sensor:
–
When connecting a return-air sensor, set parameter 4: SEL0 = 16 and SEL1 =
auto (continuous fan operation).
–
For wiring a factory-mounted return-air sensor, connect relevant CET terminals
with the corresponding terminals in the unit terminal box (refer to the unit con-
nection diagram for terminals).
Inlet temperature sensor:
–
Installation of inlet sensor in supply line
–
Fixation of sensor with an enclosed clip on the pipe. The clip is suitable for pipe
sizes of 15 mm.
–
Following sensor installation, restore the pipe insulation.
Fig. 6-47: Room sensor
Room sensor:
–
Opening of room sensor casing as illustrated.
–
Fix the casing (see Fig. 6-47) in a suitable place (see Fig. 6-48) using relevant
screws (max. M4).
–
Connect the room temperature sensor according to the wiring diagram (see
Chapter 6.13.1).
–
Close the casing in the reverse order to the opening procedure.
4+2
15
10 11 12 13 14
230V!
B A
D P
9
8
6
5
4
3
2
1
F
- +
0..10V
H
CET.EC/CET.ECH
Low voltage terminal block
LW terminal block
Parameter 2: SEL0 = 12 and SEL2 = 1
Parameter 3: SEL0 = 14 and SEL2 = OFF
(4-pipe system)
Parameter 4: SEL0 = 16 and SEL2 = auto / SEL2 = OFF
(fan continuous operation or On/Off)
Parameter 5: SEL0 = 18 and SEL2 = auto
Parameter 7: SEL0 = 22 and SEL2 = auto
Parameter 8: SEL0 = 24 and SEL2 = 2 (without sensor)
Parameter 9: SEL0 = 26 and SEL2 = 1
(automatic switch-over)
CET