Commissioning
HyCassette-Geko
109
PR-2015-0159-GB • Subject to modifications • R1-11/2015
7.6
Address setting
The appropriate group address must be assigned to the control panels and units
of a group.
Single group (without networking multiple unit groups)
•
On the control panel, set the address “0” (manufacturer's default setting).
•
On the unit PCB(s), set the “0” address (manufacturer's default setting).
Networking multiple groups
•
On the control panels and all unit PCBs assigned to the individual groups, set
the addresses to 0 -15. Each group is assigned its own address. The labels A
to F correspond to the addresses 10 to 15.
MATRIX
3500
✓
NOTICE!
Assigning duplicate addresses on the control panels can cause malfunctions.
The default setting for the group address switch is “0” and might have to be
changed.
Fig. 7-6:
Set address on the control panel
Pos. 1:
Control panel, HyCassette-Geko(s) Group 0 (Address 0)
Pos. 2:
Control panel, HyCassette-Geko(s) Group 1 (Address 1)
Pos. 3:
Control panel, HyCassette-Geko(s) Group 2 (Address 2), etc
ON
1
3
2
Group addresses
0
Group 0
8
Group 8
1
Group 1
9
Group 9
2
Group 2
A
Group 10
3
Group 3
B
Group 11
4
Group 4
C
Group 12
5
Group 5
D
Group 13
6
Group 6
E
Group 14
7
Group 7
F
Group 15
Control panel
Unit circuit boards