HyCassette-Geko
Electrical Connection
PR-2015-0159-GB • Subject to modifications • R1-11/2015
82
6.11.10
Valve connection 24 V valve
Heating, cooling, heating or cooling function; 2-pipe system
2-point modulating actuators (valve code VQ...)
Pos. 3:
Power supply 24 V AC / 50 Hz by others
Pos. 4:
Supporting terminal not always available with MATRIX
2000, have terminal installed by others on-site if re-
quired
* Remove jumper between terminal 100 and 101!
Fig. 6-25: Valve connection 2-pipe system, 2-point actua-
tors
Unit
with
MATRIX
3500
MATRIX
3500
✓
Valve
Kl. 103
Kl. STV
2-way
brown
blue
3-way
brown
blue
3-point modulating actuators (valve code VR...)
Pos. 3:
Power supply 24 V AC / 50 Hz by others
Pos. 4:
Supporting terminal not always available with MATRIX
2000, have terminal installed by others on-site if re-
quired
*Remove jumper between terminal 100 and 101!
Fig. 6-26: Valve connection 2-pipe system, 3-point modu-
lating actuators
Unit
with
MATRIX
3500
MATRIX
3500
✓
Valve
Kl. 102
Kl. 103
Kl. STV
2-way
brown
green
blue
3-way
green
brown
blue