Electrical Connection
HyCassette-Geko
101
PR-2015-0159-GB • Subject to modifications • R1-11/2015
Fan speed configuration for automatic mode
Perform configuration
To change parameters proceed as follows:
–
Set SEL0 button to 10 C
–
Set SEL2 button to stage 1,2 or 3
–
Press both SEL1 and SEL3 buttons simultaneously for more
than 10 seconds
–
Both LEDs flash alternately
–
Use SEL0 button to select the required voltage offset (see
Tab. 6-7)
–
To save voltage offset, press SEL1
for more than 5 seconds
–
The LED H/C flashes green three times after successful sav-
ing
Fig. 6-54: Switch control elements
Basic values fan
Speed 1
Speed 2
Speed 3
[mV]
1330
1670
3330
Tab. 6-6:
Basic values fan
Parameter
Position of temp. selector
SEL0 [°C]
Voltage offset [mV]
[mV]
0
10
0
1
11
333
2
12
667
3
13
1000
4
14
1333
5
15
1667
6
16
2000
7
17
2333
8
18
2667
9
19
3000
10
20
3333
11
21
3667
12
22
4000
13
23
4333
14
24
4667
15
25
5000
16
26
5333
17
27
5667
18
28
6000
19
29
6333
20
30
6667
Tab. 6-7:
Voltage offset table
NOTICE!
Calculation of the fan initial value:
Output = basic value (
see Tab. 6-6) + offset value (see Tab. 6-7).