HyCassette-Geko
Hydraulic Connection
PR-2015-0159-GB • Subject to modifications • R1-11/2015
65
5.5
Mounting lateral condensate pan
The lateral condensate pan is supplied separately and is used to collect potential
condensate from the heat exchanger connections and valves.
Circuit
Valve code
Dimen-
sion
Control valve diameter
DN 15 (½")
DN 20 (¾")
Cooling
VGC.####.0C
VGC.####.1C
VGC.####.2C
VGC.####.3C
VGC.####.4C
VGC.####.4C
VGC.####.5C
VGC.####.5C
K1
K2=K3
K2=K3
K2=K3
K2
K3
K2
K3
606
622
708
724
693
708
709
724
616
632
723
739
720
723
736
739
Heating
VGC.####.0C
VGC.####.1C
VGC.####.2C
VGC.####.3C
VGC.####.4C
VGC.####.4C
VGC.####.5C
VGC.####.5C
H1
H2=H3
H2=H3
H2=H3
H2
H3
H2
H3
556
572
658
674
628
643
644
659
566
582
673
689
667
670
683
686
Tab. 5-5:
Dimension pipework, 4-pipe, 3-way valve
NOTICE!
The given dimensions are only "approximated values". Due to adding toleranc-
es there can be differences up to 10 mm (in individual cases beyond that).
NOTICE!
On the underside of the lateral condensate pan is a sign with an illustration of
all component parts.
The material needed for installing the lateral condensate pan (extended fittings,
O-ring, perforated tape, screw and plastic rivet) is packed in a separate plastic
bag.
•
Push the O-ring on the drain connection of the lateral
condensate pan until it fits exactly in the destined groove
(Fig. 5-15pos 1+2).
•
Push the sleeve of extended fitting on the drain connection
till it fits noticeable and completely firmly. (Fig. 5-15, pos 3)
•
Push the lateral condensate pan with the top of the
extended fitting under the stop position into the
corresponding opening below the medium connection in
the casing panel of the basic unit. While doing so, tilt the
condensate pan 15° from the horizontal position towards
the longer side (Fig. 5-16, pos 1).
Fig. 5-15: Mounting extended fittings
1
2
3