Electrical Connection
HyCassette-Geko
69
PR-2015-0159-GB • Subject to modifications • R1-11/2015
6.5
Connecting mains supply voltage with controls by others (no miniature switch
control)
Pos. 1:
Power supply 230 V AC/ 50 Hz
fusing by others max. B 16 A
ensure an on-site all-pole disconnect switch is provid-
ed by others
Pos. 2:
Connection to first unit
Pos. 3:
Connection to second unit
Pos. 4:
To further units
•
Connect the mains voltage in accordance with the wir-
ing diagram on the basic PCB.
•
Units with an electric heater must be separately con-
nected to the mains voltage (see Connecting electric
heater (for units without MATRIX 3500) on page 70).
Fig. 6-4:
Connecting mains supply voltage
NOTICE!
An all-pole isolator must be provided on site by others according to the relevant
regulations!
Power supply for slave units can be provided by the master unit (refer to Fig. 6-
4, Pos. 3 and Pos. 4). Power terminals are certified for a double assignment.
The total power consumption of the units must not exceed 10 A. If required, pro-
vide an auxiliary power supply.
Only all-current sensitive fault current MCBs are permitted to be used.