Technical Description
HyCassette-Geko
22
PR-2015-0159-GB • Subject to modifications • R1-11/2015
2.5.3 Electrical data
The supply voltage is the mains supply voltage 230 V ~ 50 Hz.
Electrical data of fan motors
Electrical data for electric heater (maximum value)
Unit
type
Motor design
Capacity stage
Current consumption
[A]
1)
Power consumption [W]
2-pipe
4-pipe
SWIRL
®
AC
0
0
0.18
40
1
1
0.22
51
2
-
0.22
52
3
2
0.38
87
4
-
0.38
88
EC
1
1
0.37
45
2
-
0.39
44
4-way
AC
0
0
0.18
40
1
1
0.22
50
2
-
0.22
52
3
2
0.39
88
4
-
0.40
91
EC
1
1
0.39
47
2
-
0.42
46
1) Total fan volume flow and capacity at highest speed. Apparent current consumption is indicated for units fitted with EC
motors.
Tab. 2-10: Electrical data of fan motors at 230 V, 50 Hz
Unit type
Motor design
Capacity stage
Current consumption
[A]
Power consumption [W]
SWIRL
®
AC
1
3.26
0.75
2
6.52
1.50
EC
1
6.52
1.50
4-way
AC
0
3.26
0.75
1
3.26
0.75
2
6.52
1.50
EC
1
6.52
1.50
Tab. 2-11: Electrical data for electric heater at 230 V, 50 Hz