![Denco HyCassette-Geko Operation Manual Download Page 24](http://html1.mh-extra.com/html/denco/hycassette-geko/hycassette-geko_operation-manual_2480034024.webp)
Technical Description
HyCassette-Geko
24
PR-2015-0159-GB • Subject to modifications • R1-11/2015
2.6.2 Technical data and capacity of condensate pump
Technical data of condensate pump
2.7
Control variants and supported functions
The HyCassette-Geko with 4-way outlet is provided with the following control
system. The MATRIX 3500 control system is the premium solution based on a
BUS system. It is possible to operate with a building management system. The
CET controllers are electronic miniature switches for easy temperature and fan
regulation. On-site regulation provided by others is also possible.
HyCassette-Geko with SWIRL
®
outlet operates always with a
MATRIX 3500 control system. The entire spectrum of the SWIRL® outlet func-
tions is only available with a OP50 or OP51 control panel (see Tab. 2-15). Cali-
bration of the automatic mode via control panel is only possible using OP50 or
OP51. If other control panels are in use, calibrate by using the MATRIX.PC ser-
vice tool.
Functions like fan control, hygienic functions of the condensate pump and the
SWIRL® outlet (for SWIRL® units) are shown in Tab. 2-15. The functions using a
control system on-site (only 4-way units) depend on the functional capacity of the
applied solution.
Technical Specifications
Values
Operating voltage
220 - 240 V AC, 50/60 Hz
Max. current consumption (230V, 50/60Hz)
114/92 mA
Max. power (230V, 50/60Hz)
12/10.8 W
Sound pressure level
40 dB(A)*
* at 1 m distance from the unit and dry run of the pump
Tab. 2-13: Technical data of condensate pump
NOTICE!
The condensate pump can be operated with an on-site hose and an internal
diameter of 6 mm and a maximum length according to Tab. 2-14. The maxi-
mum allowed height difference from the bottom edge is 1.0 m. Observe the
hosepipe installation instructions described in Chapter 5.6
Height difference [m]
Max. hose lengths [m]
0.25
15
0.50
10
0.75
7.5
1.00
5
Tab. 2-14: Max. hose length