Commissioning
HyCassette-Geko
111
PR-2015-0159-GB • Subject to modifications • R1-11/2015
Minimum heating limitation (variable):
Value can fall below the set minimum temperature value if the current room tem-
perature value exceeds the setpoint by a value that is calculated as room temper-
ature difference multiplied by effective factor.
–
Advantage: Overheating of the room can be prevented or minimized by means
of the minimum limitation.
–
Disadvantage: The supply-air temperature can fall below the minimum limita-
tion temperature value.
Factory setting and enter limits for effect factor:
–
Default value
1.0
–
Minimum entered value
0.4
–
Maximum entered value
4.0
Maximum heating temperature
If this function is activated and a temperature sensor is present in supply air, a
temperature value can be entered here. This value should not exceed the supply-
air temperature.
Factory setting and entered limit values:
–
Default value
60.0 °C
–
Minimum entered value
25.0 °C
–
Maximum entered value
60.0 °C
Minimum cooling temperature
If this function is activated and a temperature sensor is present in supply air, a
temperature value can be entered here. This value should not fall below the sup-
ply-air temperature.
Factory setting and entered limit values:
–
Default value (4-way):
10.0 °C
–
Default value (SWIRL®):
13.0 °C
–
Minimum entered value
10.0 °C
–
Maximum entered value
20.0 °C
7.8
Switch on unit
HAZARDOUS VOLTAGE!
The electric switch cabinet (terminal box) is open.
Direct interventions in the electric switch cabinet (terminal box) are not permit-
ted!
Before completing work on the air handling unit, ensure that the electric switch
cabinet (terminal box) is properly closed (see Electric switch cabinet on
page 65).