Troubleshooting
8.4.1 Enable safety temperature limiter of the electric heater
This point applies only for units with electric heater.
The HyCassette-Geko electrical heating elements are monitored by a tempera-
ture-dependent switch.
In case of failure, limiting switches are activated and the electric heater is shut
down.
To enable the limiting switches proceed as follows:
•
Eliminate the cause of failure.
•
Open the electric switch cabinet.
•
Press the reset buttons inside the switch cabinet
(Fig. 6-2, Pos. 4 on Page 67 and Fig. 6-3, Pos. 4on Page 68)
"
The temperature limiting switches are unlocked and the unit is ready-to-
operate.