Chapter 4 Parameters
|
4-102
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
07.31
Motor Pole Number (Motor 2)
Unit: 1
Settings
2 to 10
Factory Setting: 4
07.32
Motor Rated Current (Motor 3)
Unit: 1
Settings
30% FLA to 120% FLA
Factory Setting: FLA
07.33
Motor No-load Current (Motor 3)
Unit: 1
Settings
0% FLA to 90% FLA
Factory Setting: 0.4*FLA
07.34
Torque Compensation (Motor 3)
Unit: 0.1
Settings
0.0 to 10.0
Factory Setting: 0.0
07.35
Slip Compensation (Used without PG) (Motor 3)
Unit: 0.01
Settings
0.00 to 10.00
Factory Setting: 0.00
07.36
Motor Line-to-line Resistance R1 (Motor 3)
Unit: 1
Settings
0 to 65535 m
Ω
Factory Setting: 0
07.37
Motor Rated Slip (Motor 3)
Unit: 0.01
Settings
0.00 to 20.00Hz
Factory Setting: 3.00
07.38
Motor Pole Number (Motor 3)
Unit: 1
Settings
2 to 10
Factory Setting: 4
The motor 0 to motor 3 can be selected by setting the multi-function input terminals MI3~MI6
(Pr.04.05 to Pr.04.08) to 27 and 28.
Summary of Contents for AC Motor Drive VFD-E
Page 1: ......
Page 2: ......
Page 3: ......
Page 13: ...This page intentionally left blank...
Page 233: ......
Page 274: ...Appendix B Accessories Revision June 2008 04EE SW PW V1 11 CTL V2 11 B 37...