Chapter 4 Parameters
|
4-62
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Settings
Function
Description
13
Over Current Stall
supervision
Active when the Over Current Stall function operating
14
Heat Sink Overheat
Warning
When heatsink overheats, it will signal to prevent OH turn off
the drive. When it is higher than 85
o
C (185
o
F), it will be ON.
15
Over Voltage supervision Active when the DC-BUS voltage exceeds level
16 PID
supervision
Active when the PID feedback signal is abnormal (Refer to
Pr.10.12 and Pr.13.)
17 Forward
command
Active when the direction command is FWD
18 Reverse
command
Active when the direction command is REV
19
Zero Speed Output
Signal
Active when the drive is standby or stop
20
Communication Warning
(FbE,Cexx, AoL2, AUE,
SAvE)
Active when there is a Communication Warning
21
Brake Control (Desired
Frequency Attained)
Active when output frequency
≥
Pr.03.11. Deactivated when
output frequency
≤
Pr.03.12 after STOP command.
22 Drive
Ready
Active when the drive is on and no abnormality detected.
23
Desired Frequency 2
Attained
Active when the desired frequency 1(Pr.03.14) is attained.
03.02
Desired Frequency 1 Attained
Unit: 0.01
03.14
Desired Frequency 2 Attained
Unit: 0.01
Settings
0.00 to 600.0 Hz
Factory Setting: 0.00
If a multi-function output terminal is set to function as Desired Frequency Attained (Pr.03.00 to
Pr.03.01=09), then the output will be activated when the programmed frequency is attained.