Chapter 4 Parameters
|
4-86
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
1
2
3
4
5
0
0=external terminal
1=internal terminal
MI1
MI2
MI3
MI4
MI5
MI6
Weights
Bit
The Setting method is convert binary number to decimal number for input.
For example: if setting MI3, MI5, MI6 to be internal terminals and MI1, MI2, MI4 to be external
terminals. The setting value should be bit5X2
5
+bit4X2
4
+bit2X2
2
= 1X2
5
+1X2
4
+1X2
2
=
32+16+4=52 as shown in the following.
0
1
0
1
1
0
Weights
Bit
0=external terminal
1=internal terminal
MI1
MI2
MI3
MI4
MI5
MI6
When extension card is installed, the number of the multi-function input terminals will increase
according to the extension card. The maximum number of the multi-function input terminals is
shown as follows.
1
2
3
4
5
0
MI1
MI2
MI3
MI4
MI5
MI6
Weights
Bit
7
8
9
10
11
6
MI7
MI8
MI9
MI10
MI11
MI12
0=external terminal
1=internal terminal
This parameter is used to set the internal terminal action via keypad, communication or PLC.
04.28
Internal Terminal Status
Unit: 1
Settings 0 to 4095
Factory Setting: 0