Appendix D How to Use PLC Function
|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
D-49
X0
M0
M1
M2
ZCP
If C10 < K10, M0 = On
If
K10 < C10 < K100, M1 = On
If C10 > K100, M2 = On
X0
K10
C10
M0
K100
=
=
3.
To clear the comparison result, use RST or ZRST instruction.
X0
RST
M0
RST
RST
M1
M2
X0
ZRST
M0
M2
API Mnemonic Operands
Function
12
MOV P
S,
D
Move
Bit Devices
Word devices
Program Steps
Type
OP
X Y M K H
KnX KnY KnM T
C
D
S
*
*
*
*
*
*
*
*
D
*
*
*
*
*
MOV, MOVP: 5 steps
Operands:
S: Source of data D: Destination of data
Explanations:
1.
See the specifications of each model for their range of use.
2.
When this instruction is executed, the content of S will be moved directly to D. When this
instruction is not executed, the content of D remains unchanged.
Program Example:
MOV instruction has to be adopted in the moving of 16-bit data.
1.
When X0 = Off, the content in D10 will remain unchanged. If X0 = On, the value K10 will
be moved to D10 data register.
2.
When X1 = Off, the content in D10 will remain unchanged. If X1 = On, the present value
T0 will be moved to D10 data register.