Chapter 4 Parameters
|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
4-55
40%
50%
60%
For 115V/230V Series
80%
90%
100%
2kHz
4kHz
8kHz
10kHz
12kHz
14kHz 15kHz
6kHz
70%
Rat
e
d Cur
rent
(%
)
Carrier
Frequency
50 with mounting method A
℃
40 with mounting method B
℃
35 with mounting method A
℃
25 with mounting method B
℃
25 with mounting method A
℃
15 with mounting method B
℃
40%
50%
60%
For 460V Series
80%
90%
100%
70%
Carrier
Frequency
Rat
e
d Cur
rent
(%
)
2kHz
4kHz
8kHz
10kHz
12kHz
14kHz15kHz
6kHz
50 with mounting method A
℃
40 with mounting method B
℃
25 with mounting method B
℃
25 with mounting method A
℃
15 with mounting method B
℃
02.04
Motor Direction Control
Factory Setting: 0
Settings
0
Forward/Reverse operation enabled
1
Reverse
operation
disabled
2
Forward
operation
disabled
This parameter is used to disable one direction of rotation of the AC motor drive direction of
rotation.