Chapter 4 Parameters
|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
4-17
Parameter Explanation
Settings
Factory
Setting
Customer
06.02
Over-Current Stall
Prevention during
Operation
0:Disable
20 to 250%
170
0: Disabled
1: Enabled during constant speed operation.
After the over-torque is detected, keep
running until OL1 or OL occurs.
2: Enabled during constant speed operation.
After the over-torque is detected, stop
running.
0
3: Enabled during accel. After the over-torque
is detected, keep running until OL1 or OL
occurs.
06.03
Over-Torque
Detection Mode
(OL2)
4: Enabled during accel. After the over-torque
is detected, stop running.
06.04
Over-Torque
Detection Level
10 to 200%
150
06.05
Over-Torque
Detection Time
0.1 to 60.0 sec
0.1
0: Standard motor (self cooled by fan)
1: Special motor (forced external cooling)
06.06
Electronic Thermal
Overload Relay
Selection
2: Disabled
2
06.07
Electronic Thermal
Characteristic
30 to 600 sec
60
0: No fault
1: Over current (oc)
2: Over voltage (ov)
3: IGBT Overheat (oH1)
06.08
Present Fault
Record
4: Power Board Overheat (oH2)
5: Overload (oL)
6: Overload1 (oL1)
7: Motor over load (oL2)
8: External fault (EF)
06.09 Second
Most
Recent Fault Record
9: Current exceeds 2 times rated current
during accel.(ocA)
0