![Delta Electronics AC Motor Drive VFD-E User Manual Download Page 206](http://html1.mh-extra.com/html/delta-electronics/ac-motor-drive-vfd-e/ac-motor-drive-vfd-e_user-manual_2476007206.webp)
Chapter 4 Parameters
|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
4-153
Parameter Explanation
Settings
Factory
Setting
Customer
8: Display the estimated value of torque as it
relates to current (t)
9: Display AVI (I) (V)
10: Display ACI / AVI2 (i) (mA/V)
11: Display the temperature of IGBT (h) (
°
C)
12: Display AVI3/ACI2 level (I.)
13: Display AVI4/ACI3 level (i.)
14: Display PG speed in RPM (G)
15: Display motor number (M)
Group 1 Basic Parameters
Parameter Explanation
Settings
Factory
Setting
Customer
01.11
Accel Time 2
0.1 to 600.0 / 0.01 to 600.0 sec
1.0
01.12
Decel Time 2
0.1 to 600.0 / 0.01 to 600.0 sec
1.0
Group 2 Operation Method Parameters
Parameter Explanation
Settings
Factory
Setting
Customer
02.00
Source of First
Master Frequency
Command
0: Digital keypad UP/DOWN keys or Multi-
function Inputs UP/DOWN. Last used
frequency saved.
1: 0 to +10V from AVI
2: 4 to 20mA from ACI or 0 to +10V from
AVI2
3: RS-485 (RJ-45)/USB communication
4: Digital keypad potentiometer
5: CANopen communication
5
0: Digital keypad
1: External terminals. Keypad STOP/RESET
enabled.
02.01
Source of First
Operation
Command
2: External terminals. Keypad STOP/RESET
disabled.
5