Chapter 4 Parameters
|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
4-107
08.12
Skip Frequency 2 Lower Limit
Unit: 0.01
08.13
Skip Frequency 3 Upper Limit
Unit: 0.01
08.14
Skip Frequency 3 Lower Limit
Unit: 0.01
Settings
0.00 to 600.0Hz
Factory Setting: 0.00
These parameters set the Skip Frequencies. It will cause the AC motor drive never to remain
within these frequency ranges with continuous frequency output.
These six parameters should be set as follows Pr.08.09
≥
Pr.08.10
≥
Pr.08.11
≥
Pr.08.12
≥
Pr.08.13
≥
Pr.08.14.
The frequency ranges may be overlapping.
0
08.09
08.10
08.11
08.12
08.13
08.14
setting frequency
in
te
rn
a
l f
re
q
u
e
n
cy
c
o
m
m
a
n
d
08.15
Auto Restart After Fault
Unit: 1
Settings
0 to 10
Factory Setting: 0
0
Disable
Only after an over-current OC or over-voltage OV fault occurs, the AC motor drive can be
reset/restarted automatically up to 10 times.
Setting this parameter to 0 will disable automatic reset/restart operation after any fault has
occurred.
When enabled, the AC motor drive will restart with speed search, which starts at the frequency
before the fault. To set the waiting time before restart after a fault, please set Pr. 08.07 Base
Block Time for Speed Search.
08.16
Auto Reset Time at Restart after Fault
Unit: 0.1
Settings
0.1 to 6000 sec
Factory Setting: 60.0