Chapter 4 Parameters
|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
4-85
0
1
0
1
1
1
0
0
0
0=Active
1=Off
MI1
MI2
MI3
MI4
MI5
MI6
MI7
MI8
MI9
Weights
Bit
When extension card is installed, the number of the multi-function input terminals will increase
according to the extension card. The maximum number of the multi-function input terminals is
shown as follows.
1
2
3
4
5
0
MI1
MI2
MI3
MI4
MI5
MI6
Weights
Bit
7
8
9
10
11
6
MI7
MI8
MI9
MI10
MI11
MI12
0=Active
1=Off
This parameter is used to select the terminals to be internal terminal or external terminal. You
can activate internal terminals by Pr.04.28. A terminal cannot be both internal terminal and
external terminal at the same time.
For standard AC motor drive (without extension card), the multi-function input terminals are
MI1 to MI6 as shown in the following.
04.27
Internal/External Multi-function Input Terminals Selection
Unit: 1
Settings 0 to 4095
Factory Setting: 0
Summary of Contents for AC Motor Drive VFD-E
Page 1: ......
Page 2: ......
Page 3: ......
Page 13: ...This page intentionally left blank...
Page 233: ......
Page 274: ...Appendix B Accessories Revision June 2008 04EE SW PW V1 11 CTL V2 11 B 37...