Appendix B Accessories
|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
B-33
Example: If you need to set up the communication speed of CME-COP01 as 500K, simply
switch BR to “5”.
BR Value
Baud rate
BR Value
Baud rate
0 10K 4 250K
1 20K 5 500K
2 50K 6 800K
3 125K 7 1M
MAC ID Setting
Rotary switches (ID_L and ID_H) set up the
Node-ID on CANopen network in hex. Setup
range: 00 ~ 7F (80 ~FF are forbidden)
01
2
3
4
5
6
7 8 9 A
B
C
D
EF
01
2
3
4
5
6
7 8 9 A
B
C
D
EF
ID_H
ID_L
Example: If you need to set up the communication address of CME-COP01 as 26(1AH),
simply switch ID_H to “1” and ID_L to “A”.
Switch Setting
Content
0 … 7F
Valid CANopen MAC ID setting
Other
Invalid CANopen MAC ID setting
B.10.4.4 LED Indicator Explanation & Troubleshooting
There are 3 LED indicators, RUN, ERROR and SP, on CME-COP01 to indicate the
communication status of CME-COP01.
RUN LED
LED Status
State
Indication
OFF
No power
No power on CME-COP01 card
Single Flash
(Green)
STOPPED
CME-COP01 is in STOPPED state
Blinking
(Green)
PRE-OPERATIONAL
CME-COP01 is in the PRE-
OPERATIONAL state
Green ON
OPERATIONAL
CME-COP01 is in the
OPERATIONAL state
Red ON
Configuration error
Node-ID or Baud rate setting error