Chapter 4 Parameters
|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
4-31
Group 13: PG function Parameters for Extension Card
Parameter Explanation
Settings
Factory
Setting
Customer
0: Disabled
1: Single phase
2: Forward/Counterclockwise rotation
13.00 PG
Input
3: Reverse/Clockwise rotation
0
13.01
PG Pulse Range
1 to 20000
600
13.02
Motor Pole Number
(Motor 0)
2 to 10
4
13.03
Proportional Gain
(P)
0.0 to 10.0
1.0
13.04
Integral Gain (I)
0.00 to 100.00 sec
1.00
13.05
Speed Control
Output Frequency
Limit
0.00 to 100.00Hz
10.00
13.06
Speed Feedback
Display Filter
0 to 9999 (*2ms)
500
13.07
Detection Time for
Feedback Signal
Fault
0.0: disabled
0.1 to 10.0 sec
1
0: Warn and RAMP to stop
1: Warn and COAST to stop
13.08
Treatment of the
Feedback Signal
Fault
2: Warn and keep operation
1
13.09
Speed Feedback
Filter
0 to 9999 (*2ms)
16
0: PG card
13.10
Source of the High-
speed Counter
1: PLC (NOT for VFD*E*C models)
Read
Only
Summary of Contents for AC Motor Drive VFD-E