Appendix D How to Use PLC Function
|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
D-27
Special D
Function
Read(R)/ Write(W)
D1025 The present value of the high-speed counter C235 (low byte)
R
D1026 The present value of the high-speed counter C235 (high byte)
R
D1027 Frequency command of the PID control
R
D1028
The value of AVI (analog voltage input) 0-10V corresponds to 0-
1023
R
D1029
The value of ACI (analog current input) 4-20mA corresponds to 0-
1023 or the value of AVI2 (analog voltage input) 0-10V
corresponds to 0-1023
R
D1030 The value of V.R digital keypad 0-10V corresponds to 0-1023
R
D1031-
D1035
Reserved --
D1036 PLC
error
code
R
D1037-
D1039
Reserved --
D1040 Analog output value
R/W
D1041-
D1042
Reserved --
D1043
User defined (when Pr.00.04 is set to 2, the register data will be
displayed as C xxx)
R/W
D1044 High-speed
counter
mode
R/W
D.4.10 Communication Addresses for Devices (only for PLC2 mode)
Device
Range
Type
Address (Hex)
X 00–17
(octal)
Bit
0400-040F
Y 00–17
(octal)
Bit
0500-050F
T 00-15 Bit/word 0600-060F
M 000-159
Bit
0800-089F
M 1000-1031
Bit
0BE8-0C07
C 0-7 Bit/word 0E00-0E07
D 00-63 Word
1000-101D
D 1000-1044 Word
13E8-1414