5.9 Connecting the Power Supply Module PSM 510
5.9.1 AC Line Choke
It is mandatory to use a 3-phase AC line choke (see
5.9.1.1 Connecting 1 PSM 510 to the AC Choke
Table 14: Line Choke Characteristics for 1 PSM 510
Model
Minimum I
rms
[A]
U
rms
[V]
Inductance [mH]
PSM 510 (10 kW)
20
500
Minimum: 0.47
Maximum: 1.47
PSM 510 (20 kW)
40
500
Minimum: 0.47
Maximum: 1.47
PSM 510 (30 kW)
60
500
0.47 ±10%
If 2 PSM 510 modules are installed in parallel, use an AC choke as specified in
5.9.1.2 Connecting 2 PSM 510 Modules to
for further information.
Table 15: Line Choke Characteristics for 2 PSM 510 installed in parallel
Model
Minimum I
rms
[A]
U
rms
[V]
Inductance [mH]
PSM 510 (2 x 30 kW)
125
500
0.24 ±10%
Danfoss recommends mounting the AC line choke close to the PSM 510.
The maximum cable length depends on the cross-section, and the required voltage and current at the DC-link.
If the AC line chokes are mounted away from the PSM 510, the maximum cable distance is 5 m.
5.9.1.1 Connecting 1 PSM 510 to the AC Choke
Connect the PSM 510 to the electric grid with the correct AC choke for the power size of the PSM 510.
Electrical Installation
Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
AQ262450196490en-000101 / 175R1170
68 | Danfoss A/S © 2019.10