6.11.7 Instantiating DAM_REF in Automation Studio™
Procedure
1. Create 1 instance of function block
DAM_REF
(located in folder
DDS_DAM
) for every Decentral Access Module (DAM) that has to be
controlled or monitored.
2. To create a link to the physical DAM, link each instance of
DAM_REF
to 1 physical DAM. This makes it the logical representation of 1
physical DAM.
Open the
Logical View
.
Initialize each instance with its node number and the slot name it is connected to (for example, IF3).
6.11.8 Instantiating ACM_REF in Automation Studio™
Procedure
1. Create 1 instance of function block
ACM_REF
(located in folder
DDS_ACM
) for every Auxiliary Capacitors Module (ACM) that has to
be controlled or monitored.
2. To create a link to the physical ACM, link each instance of
ACM_REF
to 1 physical ACM. This makes it the logical representation of 1
physical ACM.
Open the
Logical View
.
Initialize each instance with its node number and the slot name it is connected to (for example, IF3).
6.11.9 Importing a Servo Drive into Automation Studio™
Context:
NOTICE
-
For each physical servo drive, add 1 entry to the
Physical View
of Automation Studio™.
Commissioning
Operating Guide | VLT® Multiaxis Servo Drive MSD 510 System
AQ262450196490en-000101 / 175R1170| 91
Danfoss A/S © 2019.10