FB Status and control in detail
vacon · 117
24-hour support: +358 (0)201 212 575 • Email: [email protected]
7
B02: FALSE = No Action, TRUE = Fault Reset
Fault Reset: Resets active faults.
7.3
State Machine: Standard
7.3.1
Control Word: Standard
Table 52.
FB Control Word Standard
FALSE
TRUE
Comment
b0
Open CB
Charge DC
b1
b2
b3
Stop Request
Run Request
Use this for start and stop command
b4
b5
b6
b7
No Action
Fault Reset 0 > 1
Use this for fault reset
b8
b9
b10
b11
Fieldbus DIN1=OFF
Fieldbus DIN1=ON
See P2.5.1.17 -18 also WD Pulse
b12 Fieldbus
DIN2=OFF
Fieldbus
DIN2=ON
See P2.5.1.19 -20
b13 Fieldbus
DIN3=OFF
Fieldbus
DIN3=ON
See P2.5.1.21 -22
b14 Fieldbus
DIN4=OFF
Fieldbus
DIN4=ON
See P2.5.1.23 -24
b15
B00: FALSE = Open CB, TRUE = Charge DC
Open CB: The drive will stop modulating and open main circuit breaker.
Charge DC: The drive will start to precharge if the function is activated by a digital output and the
control place is fieldbus. When charging is ready, the main circuit breaker is closed depending on
“CB Close Mode” and “Enable CB Close” status.
When the control place is not fieldbus, precharge is started at a normal start command.
B03: FALSE = Stop Request, TRUE = Start Request
Stop Request: The drive will stop.
Start Request: Start Command to the drive.
B07: FALSE = No Action, TRUE = Fault Reset
Fault Reset: Resets active faults.