36 · vacon
Parameter list
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
4
4.
Parameter list
In this chapter you will find the lists of parameters that are available in this application.
4.1
Basic parameters
Table 2.
Basic parameters , G2.1
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.1.1
Grid Nom Voltage
AFE:
500V:
380V
690V:
525V
AFE:
500V:
500V
690V:
690V
Vac
500V:400
690V:690
110
Set the nominal voltage of the
grid.
Island and uGrid can go down
to 100 Vac.
Set System Nominal DC P2.1.7
P2.1.2 Grid
Nom.
Frequency 0 320 Hz 50.00 1532
Micro Grid and Island mode:
Grid Nominal Frequency
AFE Mode:
Initial start frequency.
P2.1.3
System Rated Current
0.0
Ih
A
Il
113
Used to scale % values.
P2.1.4
System Cos Phi
0.10
1.00
0.80
120
P2.1.5
System Rated kVA
0
32000
kVA
0
213
P2.1.6
System Rated kW
0
32000
kW
0
116
P2.1.7
System Nominal DC
0
1300
Vdc
500V:675
690V:931
1805
Used for DC Voltage reference
and for MCB close limit
P2.1.8 Parallel
AFE 0
1
0
1501
0 = Single AFE
1 = Parallel AFE
Activation will set DC Drooping
to 3%.
P2.1.9
Transformer: Grid
Converter Side U
0 3200
Vac 1000 1850
P2.1.10 Transformer:
Grid
Side 0 3200
Vac
1000
1851
P2.1.11
Transformer: Phase
Shift
-360
360
Deg
0.0
1852
e.g. Dyn11 = 30.0 Degree
4.2
Reference handling
Table 3.
Reference handling
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.2.1
DC Voltage Ref.
500V:
105%
690V:
105%
500V:
797 Vdc
690V:
1099 Vdc
% 110.00 1462
DC Voltage reference as % of
Nominal DC voltage = 1.35 *
Grid Nominal Voltage.
P2.2.2
Reactive Current
Reference
-170 170 % 0 1459
Regenerative reactive
current reference 100.0 =
Nominal current.
Positive =Inductive
Negative = Capacitive