Parameter list
vacon · 49
24-hour support: +358 (0)201 212 575 • Email: [email protected]
4
4.9.3
Earth fault
Table 31.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.9.3.1
Earth Fault Response
2
5
2 / Fault
1756
P2.9.3.2
Earth Fault Level
0
100
%
50
1333
4.9.4
Fieldbus fault
Table 32.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.9.4.1
FB Fault response
Slot D
0 6
2
733
P2.9.4.2
FB Fault response
Slot E
0 6
2
761
P2.9.4.3
FB WD Time
0.00
30.00
s
0.00
1354
4.9.5
External fault
Table 33.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.9.5.1
External Fault 1
0
3
2 / Fault
701
P2.9.5.2
External Fault 2
0
3
1 / Warning
1504
P2.9.5.3
External Fault Delay
0.00
320.00
s
0.00
1506
4.9.6
Grid voltage D7
Table 34.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.9.6.1 Voltage
D7
Response 0
2
1
1626
P2.9.6.2
Voltage Low Warning
Limit
0.00 320.00 %
90.00
1893
P2.9.6.3
Voltage Low Trip Limit
0.00
320.00
%
80.00
1899
P2.9.6.4
Voltage High Warning
Limit
0.00 320.00 %
110.00
1895
P2.9.6.5
Voltage High Trip Limit
0.00
320.00
%
115.00
1799
P2.9.6.6
Voltage Trip Delay
0.00
320.00
s
0.50
1898
4.9.7
Grid frequency
Table 35.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.9.7.1
Freq. Supply Response
0
2
2
1627
P2.9.7.2
Freq. D7 Response
0
2
1
1628
P2.9.7.3
Freq. Low Warning
Limit
0.00 320.00 %
95.00
1780
Low limit for e.g. Mot Pot
function
P2.9.7.4
Freq. Low Trip Limit
0.00
320.00
%
90.00
1781
P2.9.7.5
Freq. High Warning
Limit
0.00 320.00 %
106.00
1783
High limit for e.g. Mot Pot
function.
P2.9.7.6
Freq. High Trip Limit
0.00
320.00
%
110.00
1784
P2.9.7.7
Freq. Trip Delay
0.00
320.00
s
0.50
1785