Monitoring signals
vacon · 27
24-hour support: +358 (0)201 212 575 • Email: [email protected]
3
V1.3.2
FB Status Word
ID 68
This is referred as GeneralStatusWord in the fieldbus manual. See details in the fieldbus
manual.
FB Status Word ID68
Signal
Comment
b0
Ready On
0 = Drive not ready to charge
1 = Drive ready to charge
b1
Ready Run
0 = Drive not ready to run
1 = Drive ready to run and MCB is ON
b2
Running
0 = Drive not running
1 = Drive running with regenerative control ON
b3
Fault
0 = No active fault
1 = Fault is active
b4
Run Enabled
0 = Run Disabled by I/O Commands
1 = Run Enabled by I/O Commands
b5
Quick Stop
0 = Quick Stop Active
1 = Quick Stop Not Active
b6
Switch On Inhibit
0 = CB Control OK
1 = CB Requested open but DC is high
b7
Warning
0 = No warning
1 = Warning active
b8
At Reference
0 = DC Voltage Ref and Act DC Voltage are not same.
1 = DC Voltage Ref and Act DC Voltage are same.
b9
Fieldbus Control
Active
0 = Fieldbus control not active
1 = Fieldbus control active
b10
Above Limit
0 = DC voltage is below the level specified by P2.5.7.4
1 = The DC voltage is above the level specified by
P2.5.7.4
b11
FB_SW_B11
Select bit in G2.10 Fieldbus
b12
FB_SW_B12
Select bit in G2.10 Fieldbus
b13
FB_SW_B13
Select bit in G2.10 Fieldbus
b14
FB_SW_B14
Select bit in G2.10 Fieldbus
b15
Watchdog