FB Status and control in detail
P2.10.19 State machine
1 / Basic
This mode makes fieldbus control operate as is explained in the
fieldbus board manual.
2 / Standard
Simple control word that is used in modes where the control word
from fieldbus is used as such. For some fieldbus boards this
requires bypass operation.
3 / Vacon AFE 1
This mode uses a ProfiDrive type state machine in the application
level. It is possible to use this mode on fieldbus boards that do not
have a state machine or have a possibility to bypass the state
machine function on the option board.
7.1
FB DC Reference
Fieldbus DC reference is available when the Grid Converter is in fieldbus control.The format is the
same as in panel references. (11000 = 110 %). If reference is not used from fieldbus, set the
“FBSpeedReference” to zero. When FB reference is zero, the drive will use DC Voltage Reference
from keypad parameter.
7.2
State machine: Basic
7.2.1
FB Control Word Basic
Table 51.
FB Control Word: Basic
FALSE
TRUE
Comment
b0
Stop Request
Start Request
Use this for start and stop command
b1
b2
No Action
Fault Reset 0 > 1
Use this for fault reset
b3 Fieldbus
DIN1=OFF
Fieldbus
DIN1=ON
See P2.5.1.17 -18
b4 Fieldbus
DIN2=OFF
Fieldbus
DIN2=ON
See P2.5.1.19 -20
b5 Fieldbus
DIN3=OFF
Fieldbus
DIN3=ON
See P2.5.1.21 -22
b6 Fieldbus
DIN4=OFF
Fieldbus
DIN4=ON
See P2.5.1.23 -24
b7
b8
b9
b10
b11
b12
b13
b14
b15
B00: FALSE = Stop Request, TRUE = Start Request
Stop Request: Drive will stop modulating
Start Request: Drive will start modulating, rising edge needed after fault situation.