44 · vacon
Parameter list
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
4
4.5.5
Analogue output 2
Table 19.
Analogue output signals, G2.3.4
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.5.5.1 Iout
2
signal
AnOUT:0.1
AnOUT:E.10 AnOUT:A.1
464
Connect the AO1 signal to
the analogue output of your
choice with this parameter.
P2.5.5.2 Iout
Content
0
11
1 / O/P
Freq
307
0 = Not used
1 = DC Voltage
2 = Drive Current
3 = Output Voltage
4 = Active Current
5 = Power
6 = Reactive Current
7 = Power Bidirectional
8 = AI1
9 = AI2
10 = FB Analogue Output
11 = Line Voltage
12 = FreqOut, bidirectional
13 = Value Control Out
P2.5.5.3
Iout Filter
Time
0
10
s
1
308
0 = No filtering
P2.5.5.4 Iout
Invert
0
1
0 / No
Inversion
309
0 = Not inverted
1 = Inverted
P2.5.5.5
Iout
Minimum
0
1
0 / 0 mA
310
0 = 0 mA
1 = 4 mA
P2.5.5.6 Iout
Scale
10
1000
%
100 311
Percentage multiplier.
Defines output when
content is in maximum
value
P2.5.5.7 Iout
Offset -100
100
%
0
375
Add -1000 to 1000% to the
analogue output.