Description of parameters
vacon · 87
24-hour support: +358 (0)201 212 575 • Email: [email protected]
5
5.6.4
Micro Grid limits
2.6.4.1
Current Limit Minimum
An active current limit from AC to DC direction. This limit affects the Island and uGrid
operation modes but not the AFE operation mode.
2.6.4.2
Current Limit Maximum
An active current limit from DC to AC direction. This limit affects the Island and uGrid
operation modes but not the AFE operation mode.
=
~
LCL
AC
DC
Min Current Lim
Max Current Lim
Figure 33.
2.6.4.3
Maximum Limit Increase Rate
This parameter defines the increase rate for the current limit from DC to AC direction.
Input Ref.
Max Current
Limit
110 %
10 %
Internal Ref
50 % / s
2 s
Figure 34.
2.6.4.4
Current Limit Kp
The gain for the current limit operation.