Fieldbus monitoring values
V1.3.1
FB Control Word
ID 1160
The control word from fieldbus. The table below is for “2 / Vacon AFE 1” Selection
(P2.10.19) in bypass operation for such fieldbus board that natively supports this or can
be parameterised to bypass mode. See other profile selections from chapter Status and
Control Word.
FB Control Word ID1160
Signal
Comment
b0
DC Charge
0 = Open MCB.
1 = Close DC charge contactor, MCB closed automatically.
b1
b2
b3
Start
0 = Stop Command
1 = Start Command
b4
b5
b6
b7
Reset
0>1 Reset fault.
b8
b9
b10
Fieldbus
Control
0 = No control from fieldbus
1 = Control from fieldbus
b11
Watchdog
0>1>0>1…0.5 s square wave clock. This is used to check data
communication between the fieldbus master and the drive.
b12
FB DIN2
Can be used to control RO or the parameter directly by ID
number. G2.4.1
b13
FB DIN3
Can be used to control RO or the parameter directly by ID
number. G2.4.1
b14
FB DIN4
Can be used to control RO or the parameter directly by ID
number. G2.4.1
b15