114 · vacon
Description of parameters
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
5
P2.15.4
PI Max Adjust
ID360
This parameter defines maximum adjustment that PI controller can made to voltage.
5.15.1
Grid voltage PI OPT-D7 limits
These parameters define the limits within which the OPT-D7 measurements must remain in order
for the PI controller to remain active. This is a protection function is case of a measurement loss.
When a measurement loss is detected, the drive will not stop, but instead it continues to operate by
using open loop voltage compensation (Inductor Size and Losses).
P2.16.5.1 PI Frequency Low Limit
ID1630
P2.16.5.2 PI Frequency High Limit
ID1631
P2.16.5.3 PI Voltage Low Limit
ID1632
P2.16.5.4 PI Voltage High Limit
ID1633