110 · vacon
Description of parameters
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
5
P2.13.3 Synch
Gain
1778
The phase synchronisation gain. The frequency reference at 180 degree difference.
P2.13.4
Phase Synch Ramp Time
1777
The ramp time for the synchronisation function. When the synchronisation mode is after
the ramp, this time is active all the time.
If the synchronisation mode is before ramp, this time is activated when the angle
difference is less than the value of Ramp Change Hyst.
P2.13.5
Max Synch Correction 1992
This parameter defines how much correction the phase synchronisation can make. The
value 3070 equals to Synch Gain value.
P2.13.6
Ramp Change Hysteresis.
1894
This parameter defines the limit when the phase synchronisation starts to use the ramp
time defined by P2.13.4. Before this, ramp time P2.3.1 is used.
5.14
ID functions
Here you will find the functions that use the parameter ID number to control and monitor the signal.
5.14.1
Value control
The value control parameters are used to control an input signal parameter.
P2.14.1.1 Control Input Signal ID ID1580
“ContrInSignal ID”
With this parameter you can select which signal is used to control the selected
parameter.
P2.14.1.2 Control Off Limit
ID1581
“Contrl Off Limit”
This parameter defines the limit when the selected parameter value is forced to Off
value.
P2.14.1.3 Control On Limit
ID1582
“Contrl On Limit”
This parameter defines the limit when the selected parameter value is forced to On
value.
P2.14.1.4 Control Off Value
ID1583
“Contrl Off Value”
This parameter defines the value that is used when the used input signal is below Off
limit.
P2.14.1.5 Control On Value
ID1584
“Contrl On Value”
This parameter defines the value that is used when the used input signal is above On
limit.