Parameter list
vacon · 45
24-hour support: +358 (0)201 212 575 • Email: [email protected]
4
4.5.6
Analogue output 3
Table 20.
Analogue output signals, G2.3.4
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.5.6.1 Iout
3
signal
AnOUT:0.1
AnOUT:E.10 AnOUT:A.1
464
Connect the AO1 signal to
the analogue output of your
choice with this parameter.
P2.5.6.2 Iout
Content
0
11
1
307
0 = Not used
1 = DC Voltage
2 = Drive Current
3 = Output Voltage
4 = Active Current
5 = Power
6 = Reactive Current
7 = Power Bidirectional
8 = AI1
9 = AI2
10 = FB Analogue Output
11 = Line Voltage
12 = FreqOut, bidirectional
13 = Value Control Out
P2.5.6.3
Iout Filter
Time
0
10
s
1
308
0 = No filtering
P2.5.6.4 Iout
Invert
0
1
0 / No
Inversion
309
0 = Not inverted
1 = Inverted
P2.5.6.5
Iout
Minimum
0
1
0 / 0 mA
310
0 = 0 mA
1 = 4 mA
P2.5.6.6 Iout
Scale
10
1000
%
100 311
Percentage multiplier.
Defines output when
content is in maximum
value
P2.5.6.7 Iout
Offset -100
100
%
0
375
Add -1000 to 1000% to the
analogue output.
4.5.7
Options
Table 21.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.5.7.1 Output
Inversion 0 65535
0
1806
P2.5.7.2
Freq Scale Min AO
0.00
320.00
Hz
0.00
1809
P2.5.7.3
Freq Scale Max AO
0.00
320.00
Hz
50.00
1808
P2.5.7.4
DC Supervision Limit
0
1500
V
1454
P2.5.7.5 MCB
Close
Mode 0
2
0
1607
0 = DC Voltage
1 = DC or Start command
2 = Start Command.
P2.5.7.6
MCB At Stop
Command
0 1
0 1685
0 = Keep CB Closed
1 = Open CB
P2.5.7.7
MCB Close Delay
0.00
3.00
0.00
1513
Delay to CB RO