52 · vacon
Parameter list
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
4
4.11
Micro Grid
Table 40.
Micro Grid, G2.7
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.11.1
Control Mode
0
6
0 / AFE
1531
0 = AFE
1 = Island
2 = Micro Grid
3 = Island-AFE
4 = Island-Micro Grid
5 = Island-Micro Grid
(Reserved)
6 = FreeSelect
P2.11.2 Frequency
Droop
1
32
Hz
1
1534
P2.11.3 Voltage
Droop
0
320 %
10
1535
Reactive current drooping in
percentage of P2.1.
P2.11.4
Start Power Mode
0
2
2
1503
0 = Zero power D7
1 = Zero Power F/O
2 = Drooping
3 = Isochron.Gen
P2.11.5 Voltage
Rise
Time
0
10000
ms
100
1541
P2.11.6
Generator
Mechanical Time
Constant
0 32000
ms
0 1722
0 = Not used
1 >= Active
Use 1000 ms as a starting
point.
P2.11.7
Generator Speed
Control Kp
0,0 3200,0
%/Hz 40,0 1723
P2.11.8
Generator Speed
Control Yi
0 32000
ms 32000 1724
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.11.10.1
AFE Mode 1
0
6
0 / AFE
1616
P2.11.10.2
AFE Mode 2
0
6
1 / Island
1617
P2.11.10.3
AFE Mode 3
0
6
2 / Micro Grid
1713