120 · vacon
FB Status and control in detail
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
7
B06: FALSE = CB Control OK, TRUE = CB Control Not OK
CB Control OK: CB control and the drive internal status are the same.
CB Control Not OK: The drive internal status to close the circuit breaker is high but the application
logic requests for the circuit breaker to open. This can be the case when CB has been opened but DC
is connected to battery system. DC must be discharged or CB must close.
B07: FALSE = No Warning, TRUE = Warning Present
No Warning: There is no warning or the warning has disappeared again.
Warning Present: The drive operates, but there is an active warning.
B08: FALSE = DC Voltage out of tolerance TRUE = DC Voltage within tolerance
DC Error Out Of Tolerance Range
DC Error Within Tolerance Range
B09: FALSE = No Control Requested, TRUE = Control Requested
No Control Requested: Control by the automation system is not possible, only possible at the device
or by another interface.
Control Requested: The automation system is requested to assume control.
B10: FALSE = DC Not Reached, TRUE = DC Reached Or Exceeded
DC Not Reached: DC is below P2.5.7.4 DC Voltage Supervision Limit.
DC Reached Or Exceeded: DC is above P2.5.7.4 DC Voltage Supervision Limit.
B11: FALSE = SW ID.Bit selection B11, TRUE = SW ID.Bit selection B11
SW ID.Bit selection B11 Low: Selected bit is low.
SW ID.Bit selection B11 High: Selected bit is high.
B12: FALSE = SW ID.Bit selection B12, TRUE = SW ID.Bit selection B12
SW ID.Bit selection B12 Low: Selected bit is low.
SW ID.Bit selection B12 High: Selected bit is high.
B13: FALSE = SW ID.Bit selection B13, TRUE = SW ID.Bit selection B13
SW ID.Bit selection B13 Low: Selected bit is low.
SW ID.Bit selection B13 High: Selected bit is high.
B14: FALSE = SW ID.Bit selection B14, TRUE = SW ID.Bit selection B14
SW ID.Bit selection B14 Low: Selected bit is low.
SW ID.Bit selection B14 High: Selected bit is high.
B15: FALSE = FB DW Feedback Low, TRUE = FB DW Feedback High
FB DW Feedback: FB Control Word B11 is echoed back to the fieldbus. Can be used to monitor the
communication status from the drive.