Parameter list
vacon · 55
24-hour support: +358 (0)201 212 575 • Email: [email protected]
4
4.14.4
DIN ID control 3
Table 46.
DIN ID control parameters, G2.2.8
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.14.4.1
ID Control DIN
0.1
E.10
0.1
1578
Slot Board input No.
If 0.1 ID61 can be
controlled from FB
P2.14.4.2 Controlled
ID
0 10000 ID
0
1579
Select ID that is
controlled by digital input
P2.14.4.3
False value
-32000
32000
0
1594
Value when DI is low
P2.14.4.4
True value
-32000
32000
0
1596
Value when DI is high
4.14.5
DIN ID control 4
Table 47.
DIN ID control parameters, G2.2.8
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.14.5.1
ID Control DIN
0.1
E.10
0.1
1930
Slot Board input No.
If 0.1 ID61 can be
controlled from FB
P2.14.5.2 Controlled
ID
0 10000 ID
0
1931
Select ID that is
controlled by digital input
P2.14.5.3
False value
-32000
32000
0
1932
Value when DI is low
P2.14.5.4
True value
-32000
32000
0
1933
Value when DI is high
4.15
Auto reset
Table 48.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.15.1 Wait
Time 0.00
60.00
s
5.00
717
P2.15.2 Trial
Time 0.00
120.00
s
30.00
718
P2.15.3
Over voltage tries
0
3
0
721
P2.15.4
Over current tries
0
3
0
722
P2.15.6
External fault tries
0
10
0
725
4.16
Grid voltage PI
Table 49.
Grid voltage PI function
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.16.1 PID
Activation 0.1 E.10
DigIn 0.1 1807
Digital input to activate PI
controller
P2.16.2
PI controller gain
0.0
1000.0
%
200.0
118
PI controller gain
P2.16.3
PI controller I-time
0.00
320.00
s
0.05
119
PI controller I-time
P2.16.4
PI Max Adjust
-32000
32000
%
5.00
360
PI High limit
P2.16.5.1
PI Frequency Low
Limit
0.00 320.00 % 95.00
1630
P2.16.5.2
PI Frequency High
Limit
0.00 320.00 % 102.00 1631
P2.16.5.3
PI Voltage Low
Limit
0.00 320.00 % 90.00
1632
P2.16.5.4
PI Voltage High
Limit
0.00 320.00 % 110.00 1633